3.5.
Neutral Power System
A TN-S neutral point connection system is mandatory for the equipment. To construct the
system, a protective conductor (PE) is connected to the neutral conductor at the origin of the
installation. As the Neutral and the PE wire are connected to the same output point of the
source, the voltage measured between “Neutral” and “Ground” at any point in the
installation must approach 0 Volt.
At the secondary winding of the power supply interface, the Neutral point is directly
connected to the grounding shaft measurement strip, or to the nearest outlet. This connection
is called the “Neutral reference wire”.
DANGER
When defining a neutral point connection, the output Neutral point of a power source or
power supply interface must always be directly connected (referenced) to the nearest
grounding shaft strip and never to a grounding point.
mportant The equipment grounding conductor wire (PE) must be integrated in the
same wireway as the phase and neutral wires.
Figure 14. Grounding circuit diagram for a TN-S neutral point connection
3-8