3.4.
Grounding Circuit
The electronic components inside the equipment are sensitive to high-frequency
electromagnetic interference. To ensure correct hardware operation, high-frequency
interference must be limited via an equipotential ground circuit and metallic braid shielded
cables.
DANGER
For the protection of personnel and hardware, it is mandatory for the grounding network to
be compliant with Data Processing Center requirements and the standards in force.
A single, equipotential grounding circuit dedicated to data processing systems is required. If
the building has several, separate grounding shafts, it is mandatory for them to be
interconnected to eliminate the occurrence different transient potentials within the same unit.
3.4.1.
Electric Protection Wire Characteristics
CAUTION
Electric protection wire characteristics must be compliant with the Standards NF C15.100 and
EN 50174-2 in force:
•
•
•
•
•
flexible,
multi-strand,
black, noise-free grounding wire,
insulated along its entire length,
cross-section: 25 mm
2
- 95 mm
2
according to Data Processing Center configuration.
3-6
- Site Preparation Guide