DANGER Notices
DANGER Notices call attention to the presence of hazards that have the potential of causing
death or serious personal injury.
DANGER
An AC power supply compliant with the Lightning Protection Standards NF C15.100 and IEC
62305 in force is mandatory.
DANGER
• To ensure the protection of personnel and equipment, bipolar magneto-thermic circuit
breakers must be installed on the phase and neutral wires, in compliance with the safety
standards in force.
• Power must be exclusively conveyed by copper conductors from the source. Aluminium
conductors are prohibited. It is mandatory to separate the power supply for the
equipment from the non-computing power supply.
DANGER
For the protection of personnel and hardware, it is mandatory for the grounding network to
be compliant with Data Processing Center requirements and the standards in force.
A single, equipotential grounding circuit dedicated to data processing systems is required. If
the building has several, separate grounding shafts, it is mandatory for them to be
interconnected to eliminate the occurrence different transient potentials within the same unit.
DANGER
When defining a neutral point connection, the output Neutral point of a power source or
power supply interface must always be directly connected (referenced) to the nearest
grounding shaft strip and never to a grounding point.