51
FRYO PI
COSMOGAS
9 - MAINTENANCE
9.9 - Troubleshooting
Fault
Cause
Solution
The appliance don’t start
1. No power supply.
Check the power supply.
2. The fuse on the gas side control board
has tripped or the switch is open.
Verify that the circuit is not open and that it is properly
grounded. Replace the fuse and reset the switch. Check
that the circuit is stable and that the connections are well
done.
3. Some protection has intervened.
Identify the protection intervened, restore it and restart
the appliance.
4. Slow wiring.
Check the electrical wiring and tighten the connections.
5. Compressor broken.
Replace the compressor.
The fan don’t work
1. Wiring motor not connected.
Check the wiring motor.
2. Fan motor fault.
Replace the fan motor.
Low heating performance
1. The plate heat exhanger is dirty.
Clean the plate heat exchanger.
2. Ventilation is insufficient.
Remove the objects that prevent air circulation.
3. Insufficient refrigerant.
Check that there are no leaks in the appliance and
system, if necessary repair them. Replace the refrigerant
with new product and correct quantity.
4. Temperature out of range
Check that the setpoint temperature is not too high in
heating or too low in cooling.
Abnormal noise from the pump or no
water circulation while the pump is
running
1. Water loss in the circuit.
Check the filling tap, fill the circuit with the right amount
of water.
2. Air in the hydraulic circuit.
Remove air from the circuit.
3. The valves in the hydraulic circuit are
not fully open.
Verify that all valves are fully open.
4. The water filter is dirty or clogged.
Clean the filter or replace it.
Compressor discharge pressure too
high
1. Too much refrigerant.
Replace the refrigerant with new product and correct
quantity.
2. Air in the refrigerant circuit.
Replace the refrigerant with new product and correct
quantity.
3. Inadequate water flow.
Check the water flow in the circuit, if necessary use a
more performing pump.
4. Too high temperature.
Make sure that the water supply temperature sensor
works properly.
Suction pressure too low
1. Dirty filter drier.
Replace the filter drier.
2. Electronic expansion valve blocked.
Repair or replace it.
3. Loss of refrigerant.
Check that there are no leaks in the appliance and in the
system, if necessary repair them. Replace the refrigerant
with new product and in the correct quantity.
The appliance does not complete the
defrost cycle
1. Expansion battery sensor fault.
Check the position and value of the temperature sensor,
if necessary replace it.
2. Ventilation is insufficient.
Eliminate objects that prevent air circulation. If necessary,
clean the evaporation battery.
Содержание FRYO 6PI
Страница 2: ......
Страница 58: ...58 FRYO PI COSMOGAS...
Страница 59: ...59 FRYO PI COSMOGAS...
Страница 60: ...COSMOGAS s r l Via L da Vinci 16 47014 MELDOLA FC ITALY info cosmogas com www cosmogas com...