14
FRYO PI
COSMOGAS
4.2.3 - Connection with puffer tank in parallel
Figure 4-4 - Hydraulic diagram with puffer tank in parallel
LEGEND of Figure 4-4:
1 - Heat pump
2 - Filter
3 - Pressure safety valve
4 - Pressure meter gauge
5 - Pump
6 - Puffer tank
7 - “Tc” sensor
8 - “Th” sensor
10 - System filling water inlet
11 - Non-return valve
12 - Heating / cooling supply manifold
13 - Heating / cooling return manifold
17 - Integrative electrical resistance (optional)
18 - Expansion tank
40 - E/I = Summer / winter diverter (to be provided if the machine is both heating and cooling).
41 - TA = RT Room Temperature
Items “2” to “18” must be field supplied.
The “Tc” (7) and “Th” (8) sensors are fixed inside the appliance on the supply tube. To place them on the tank, remove
the cover and the frontal cover of the appliance, remove the two sensors and place them on the tank using the extension
cables supplied in the accessories bag (section 5.7.4).
Connect any integrative electrical resistance (17) with the interposition of a relay suitable for the electrical absorption of
the installed resistance (section 5.7.3).
Modify the operation of the internal pump, in this way the circulator will switch off 60 seconds after the compressor is
switched off: set Parameter “A1” to 0
. (section 7.5).