4.2.5 - Connection with DHW production (single coil tank loaded by plate heat
exchanger) plus solar (optional) plus direct connection to the system
Figure 4-6 - Hydraulic diagram with DHW production (single coil tank loaded by plate heat exchanger)
plus solar (optional) plus direct connection to the system
LEGEND of Figure 4-6:
1 - Heat pump
2 - Filter
3 - Pressure safety valve
4 - Pressure meter gauge
5 - Water inlet
6 - Coil tank
7 - Domestic hot water outlet
8 - Diverter valve
9 - Solar tank sensor
10 - System filling water inlet
11 - Non-return valve
12 - Heating / cooling supply manifold
13 - Heating / cooling return manifold
4 - FUNCTION OVERVIEW
14 - “Tw” DHW temperature sensor
15 - Electric resistance power supply
16 - Solar panel sensor
17 - Integrative electrical resistance (optional)
18 - Expansion tank
19 - Solar control board
20 - Solar pump
21 - Solar expansion tank
22 - Solar panel
23 - Pump
40 - E/I = Summer / winter diverter (to be provided if the
machine is both heating and cooling).
41 - TA = RT Room Temperature
Except for items “1” and “14”, all items must be field supplied.
The “Tw” sensor (14), supplied with the appliance, must be positioned on the tank using the extension cable connected
to the “Tw” terminal (Figure 5-10), present in the electrical connection compartment (Figure 3-1). Enable DHW operation
via the system settings: Parameter “08” = 2. (section 7.5).
Connect any integrative electrical resistance (17) to a thermostat (15).
Set the integrative electrical resistance point (17), using the integrative electric resistance thermostat (15), at 5 ° C lower
than the domestic hot water set point.
WARNING !!! If you use this scheme,
you must to provide a sanitization system
against the Legionella bacterium.