GEMTEQ I/O 6. GEMTEQ I/O Modules
If the GEMTEQ I/O module is fitted to the end of a GEMCAN network, then they should be wired
up as per Figure 6-2.
0 V
CAN L
Scn
CAN H
(Fit Link for
Network Termination)
1
2
3
4
5
CAN B
CAN A
TH
L
0
v
Scn
T
H
L
0
v
Sc
n
PL
4
PL
5
GEMTEQ I/O Technical Manual (T2031En)
Rev.02 (10/10)
Page 6-5
4
T
Figure 6-2
CAN Network Connections – End of Link
If for any reason the device on the end of the GEMCAN link needs to be able to be disconnected,
while maintaining the operation of all other devices, then a 120 Ohm resistor should be fitted
between CAN_H and CAN_L, in place of the link between terminals 4 & 5.
6.4.2
Power Supply Connections
A 24V d.c. power supply should be connected to PL7, as detailed in Figure 6-3.
24V dc
0V
PL7
Module Supply
24V dc
Figure 6-3
GEMTEQ I/O Module – Power Supply Connections
6.4.3
Plant I/O Connections
Details of the plant I/O connections can be found in the appropriate module Instruction Sheet.