GEMTEQ I/O 4. GEMCAN I/O Scanner Configuration
4.2.3 Baud
Rate
Module 1 (Port A Px+2, Port B Px+13) / Module 2 (Port C Px+31, Port D Px+42)
Range
0 to 8
All devices on a GEMCAN network must operate at the same Baud Rate.
Table 4-3
GEMCAN I/O Scanner - Baud Rate Selection & Maximum Bus Length
Value
Baud Rate
Transfer Rate in
PDOs per second
Maximum Bus Length (m)
0 1M
10000
30
1 800k 8000
50
2 500k 5000
100
3 250k 2500
250
4 125k 1250
500
5 100k 1000
650
6 50k 500
1000
7 20k 200
2500
8 10k 100
5000
Note: The individual GEMTEQ module baud rate is configured by setting switch 5 on the unit,
please refer to the relevant module data sheet.
4.2.4 Port
Mode
Module 1 (PortA Px+3, PortB Px+14) / Module 2 (PortC Px+32, PortD Px+43)
Operating Mode Range
0 to 4
Port Sub Mode
Range
0 to 1
x
Port Sub Mode
range (0 to 1)
High byte
Operating Mode
range (0 to 4)
Low byte
y
4.2.4.1 Operating Mode ( X )
The GEMCAN I/O Scanner module has four modes of operation, as detailed in Table 4-4 below.
Further explanation of these modes may be found in Section 3.
Table 4-4
GEMCAN I/O Scanner - Operating Mode
GEMTEQ I/O Technical Manual (T2031En)
Page 4-4
Operating Mode
Description
0 Not
Configured
1 Slave
2 Standard
Master
3 Redundant
Master
Rev.02 (10/10)
Содержание GEMTEQ I/O GEM80
Страница 1: ...GEM80 GEMTEQ I O Series Controllers Publication No T2031En Rev 02 10 10 Technical Manual ...
Страница 2: ...This page intentionally left blank ...
Страница 28: ...GEMTEQ I O 3 GEM80 GEMCAN NETWORK GEMTEQ I O Technical Manual T2031En Page 3 8 Rev 02 10 10 ...
Страница 30: ...GEMTEQ I O 3 GEM80 GEMCAN NETWORK GEMTEQ I O Technical Manual T2031En Page 3 10 Rev 02 10 10 ...
Страница 44: ......
Страница 102: ......