GEMTEQ I/O 4. GEMCAN I/O Scanner Configuration
4.
GEMCAN I/O SCANNER CONFIGURATION
4.1 INTRODUCTION
This section describes the P-Table configuration data that is required to allow a GEMCAN I/O
Scanner module to take part in the data exchanges on a GEMCAN network, either as a Master or
as a Slave device.
4.2
GEMCAN I/O SCANNER CONFIGURATION DATA
The GEMCAN I/O Scanner module(s) configuration parameters must be entered into the
P-Table of the host GEM80 controller by the user before the module(s) can be used. These
parameters are read by the GEMCAN I/O Scanner on power-up and whenever a re-compile is
performed of the host controller.
For the GEMCAN I/O Scanner module(s) to access the configuration data successfully, a value
must be written into P73. This value acts as a pointer to the first P-Table location containing
GEMCAN I/O Scanner configuration data, e.g. if P73 contains a value of 500, configuration data
begins at P500. The user must ensure that there are sufficient “P” tables declared for the
configuration data.
Inserting a value of 0 into P73 renders inactive all GEMCAN I/O Scanner modules belonging to
the host controller.
A detailed description of each configuration parameter is provided in the following paragraphs.
Table 4-1 provides a reference table for the configuration data.
Table 4-1
P-Tables reserved for GEMCAN I/O Scanner Configuration Data
P-Table Value Description
P73
Pointer to the GEMCAN I/O Scanner Configuration
Data
Px
@CAF1 Module 1: Validity Flag
See 4.2.1
Px+1
Module 1, Port A : CAN Node ID
See 4.2.2
Px+2
Module 1, Port A : Baud Rate
See 4.2.3
Px+3
Module 1, Port A : Port Mode / Sub Mode
See 4.2.4
Px+4
Module 1, Port A : Master C/O Time mS
See 4.2.5
Px+5
Module 1, Port A : Max. Input Data Delay mS
See 4.2.6
Px+6
Module 1, Port A : Max. Output Data Delay mS
See 4.2.7
Px+7
Module 1, Port A : Split Offset (Must always be
zero)
See 4.2.8
Px+8
Module 1, Port A : Sync Period mS
See 4.2.9
Px+9
Module 1, Port A : Node Guard Period mS
See 4.2.10
Px+10
Reserved
Px+11
Reserved
Px+12
Module 1, Port B : CAN Node ID
See 4.2.2
Px+13
Module 1, Port B : Baud Rate
See 4.2.3
Px+14
Module 1, Port B : Port Mode
See 4.2.4
Px+15
Module 1, Port B : Master C/O Time mS
See 4.2.5
Px+16
Module 1, Port B : Max. Input Data Delay mS
See 4.2.6
GEMTEQ I/O Technical Manual (T2031En)
Rev.02 (10/10)
Page 4-1
Содержание GEMTEQ I/O GEM80
Страница 1: ...GEM80 GEMTEQ I O Series Controllers Publication No T2031En Rev 02 10 10 Technical Manual ...
Страница 2: ...This page intentionally left blank ...
Страница 28: ...GEMTEQ I O 3 GEM80 GEMCAN NETWORK GEMTEQ I O Technical Manual T2031En Page 3 8 Rev 02 10 10 ...
Страница 30: ...GEMTEQ I O 3 GEM80 GEMCAN NETWORK GEMTEQ I O Technical Manual T2031En Page 3 10 Rev 02 10 10 ...
Страница 44: ......
Страница 102: ......