GEMTEQ I/O 6. GEMTEQ I/O Modules
6.3 MODULE
CONFIGURATION
Before a GEMTEQ I/O module may be connected to the GEMCAN network, the following two
items must be setup on the module.
•
Node
ID
•
Baud
Rate
6.3.1 Node
ID
Each device on a GEMCAN network must have a unique Node ID. This is setup on the
hexadecimal rotary switches SW3 and SW4, as detailed below.
Table 6-2
GEMTEQ I/O Module – Node ID Selection
SW3 / SW4
Switch Position
Value
0 0
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
A 10
B 11
C 12
D 13
E 14
F 15
SW3 = 7, SW4 = D NODE ID = (7*16) + 13 = 125
SW3 = 1, SW4 = 6 NODE ID = (1*16) + 6 = 22
SW3 = 0, SW4 = A NODE ID = 10
e.g.
Node ID =
(SW3 *16) + SW4
The Node ID determines which C/D tables are used within the GEM80-500 controller to
communicated with the slave modules ( see Appendix A ).
GEMTEQ I/O Technical Manual (T2031En)
Rev.02 (10/10)
Page 6-3
Содержание GEMTEQ I/O GEM80
Страница 1: ...GEM80 GEMTEQ I O Series Controllers Publication No T2031En Rev 02 10 10 Technical Manual ...
Страница 2: ...This page intentionally left blank ...
Страница 28: ...GEMTEQ I O 3 GEM80 GEMCAN NETWORK GEMTEQ I O Technical Manual T2031En Page 3 8 Rev 02 10 10 ...
Страница 30: ...GEMTEQ I O 3 GEM80 GEMCAN NETWORK GEMTEQ I O Technical Manual T2031En Page 3 10 Rev 02 10 10 ...
Страница 44: ......
Страница 102: ......