GEMTEQ I/O 8. Maintenance and Fault Finding
GEMTEQ I/O Technical Manual (T2031En)
Page 8-4
Code in F330 or F333
Condition
Comment
Numeric
Value (dec)
States
On
Fault
or
Warning
513
9 & 0
Fault
Table allocation fault
Incorrect allocation of C/D-
Tables.
Modify user program.
8.2.2 Communications
Statistics
A set of communications statistics is maintained for each active GEMCAN I/O Scanner port, as
detailed in Table 8-4.
Table 8-4
Communications Statistics
Module 1
Module 2
Description
F336 F341 Status
0
=
Offline
1
=
Online
2 = Bus Off
3 = Error / Warning
F337
F342
Tx Count per second
F338
F343
Rx Count per second
F339
F344
Bus Off Count per second
F340
F345
Operational State
01 = Disconnected
02
=
Connecting
03
=
Preparing
04
=
Stopped
05
=
Operational
7D
=
Reset
Communications
7E
=
Initialising
7F
=
Pre-operational
Note
Loss of an individual node ID will not produce an error/warning status, however loss of all
communications will produce an error / warning i.e. Status = 3.