GEMTEQ I/O 6. GEMTEQ I/O Modules
6.6.3.1 Freeze/Fallback Timeout (mS)
Range
1 to 32000 mS
0 = 500 mS (Default)
If the application requires the default freeze/fallback time to be overridden then a value can be
transmitted to the module in the Freeze/Fallback Time. For further details please refer to the
appropriate Instruction Sheet.
6.6.3.2 Freeze/Fallback
Value
By using one bit per channel (Bit 0 = Channel 0), this signifies whether freeze or fallback should
be adopted, when loss of Node Guard messages has been detected by the I/O module.
0
Fallback to zero
1
Freeze present value
For further details please refer to the appropriate Instruction Sheet.
6.6.4
Analog Input – Voltage or Current Input Mode
By using one bit per channel (Bit 0 = Channel 0), this signifies whether the Analog I/P channel
should operate as Voltage or Current input mode.
0
Voltage Input mode
1
Current Input mode
6.6.5
Analog Input – 0-20mA or 4-20mA Input Mode
By using one bit per channel (Bit 0 = Channel 0), this signifies whether the Analog I/P channel,
when configured in Current input mode, should operate as 0 to 20mA or 4 to 20mA.
0
0 to 20mA input mode
1
4 to 20mA input mode
GEMTEQ I/O Technical Manual (T2031En)
Page 6-8
Rev.02 (10/10)
Содержание GEMTEQ I/O GEM80
Страница 1: ...GEM80 GEMTEQ I O Series Controllers Publication No T2031En Rev 02 10 10 Technical Manual ...
Страница 2: ...This page intentionally left blank ...
Страница 28: ...GEMTEQ I O 3 GEM80 GEMCAN NETWORK GEMTEQ I O Technical Manual T2031En Page 3 8 Rev 02 10 10 ...
Страница 30: ...GEMTEQ I O 3 GEM80 GEMCAN NETWORK GEMTEQ I O Technical Manual T2031En Page 3 10 Rev 02 10 10 ...
Страница 44: ......
Страница 102: ......