2-42
1010PVNFM-3A
Section 2
NOTE: NETFLOW (default) is best for applications where there may be zero flow for
long periods. It minimizes false Totalizer register increments due to data scat-
ter. Press the <Down Arrow> to accept the default setting.
To select a Totalizer Mode:
To access the [Totalizer Mode] option list press
Move the cursor to the required Totalizer mode by pressing
To store selection press
2.6.9 BATCH/SAMPLE TOTAL
The meter maintains a separate totalizer register for Batching or Sampling applications. Un-
like the Flow Total registers, you cannot access this register directly. It is used for re-
lay control only. If you assign the system relay to this function, a momentary (200 mS) relay
pulse occurs whenever the BATCHTOT register accumulates a specified liquid quantity. You
enter the total flow volume required to activate the relay, in the Batch/Sample Total menu
cell. The numeric entry must reflect the selected flow total units. The Totalizer Display Scal-
ing menu cell shows the applicable flow total units. The sign of the Batch/Sample Total deter-
mines positive or negative accumulations.
NOTE: The Batch/Sample total relay requires the same consideration for ex-
ceeding the maximum pulse rate as the TOTCNT relay (see Total Resolution).
To enter a Batch/Sample Volume:
To activate numeric entry press
Use the numeric keys to type the desired Batch/Sample TOT accumulation.
To store data press
2.7
THE DATA SPAN/SET/CAL MENU
This menu becomes available after picking a Meter Type and Measurement Channel. How-
ever, some functions will only be active after the transducers are installed and operating
properly.
Use the [Data Span/Set/Cal] menu to set the range for analog outputs and setpoints for Alarm
relay outputs. Additionally, the [Calibrate Flowrate] menu allows you to apply external ad-
justments to the meter’s intrinsic primary outputs.
ENT
ENT
MODE FLOW DIRECTION
NOTES
POSFLOW
positive flow
Accumulates flow in positive direction only
NEGFLOW
negative flow
Accumulates flow in reverse direction only
NETFLOW
positive or negative Adds to positive total; subtracts from reverse total
2.6.8 TOTALIZER MODE
The Totalizer function operates in any of the modes listed below: