X-600M Users Manual
Appendix I: Specifications
Appendix I: Specifications
Power Requirements
Input Voltage:
9-28 VDC (24V power supply recommended)
Input Current:
See table below for typical values at 25°C,10/100Mbps.
Expansion bus is powered via the
Vin+
terminal
Power
Supply
Input Current
(no expansion modules)
Input Current
(X-600M + 1.7A for expansion modules)
9 VDC
200 mA
1.90 Amps
12 VDC
150 mA
1.85 Amps
24 VDC
80 mA
1.78 Amps
Voltage Outputs
Expansion Bus:
1.70A max
5-VDC (for 1-wire bus):
50mA max
I/O Connector
Type:
5-position, removable, 3.81 mm pitch
Connection wire:
Use wire rated for 75ºC (min) for connections to the terminal blocks
Stripping Length:
7mm
Connection capacity:
1.5mm
2
stranded, 1.5mm
2
solid
Conductor minimum:
30AWG (UL/CUL)
Conductor maximum:
14 AWG (UL/CUL)
Conductor Type:
Copper
Tightening torque:
0.22 Nm (min), 0.25 Nm (max)
(Replacement part number, Phoenix Contact 1827004)
USB:
Host:
USB 2.0 Type A
Device:
USB 2.0 Mini-B
Expansion Connector:
Provides power and communication for expansion modules.
Connector:
Ribbon cable,10-conductor, polarized, 2x5-position, 0.100” pitch
Communications: EIA/TIA-485
Internal Temperature Sensor
Type: digital, 1-wire, (Dallas Semiconductor DS18B20) -40°C to +85°C
External 1-Wire Temperature/Humidity Sensors
Sensors:
32 maximum at short distance. Different combinations of cable length
and sensor types will have different results (e.g., supports 10
temperature sensors and 2 humidity sensors at 550 feet).
Cable Length:
600 ft (180 m) maximum combined cable length
Temperature Sensor:
Dallas Semiconductor DS18B20 digital 1-wire thermometer
+/-0.5°C from -10°C to +85°C
Temp & Humidity Sensor: ControlByWeb X-DTHS-WM wall mount sensor
+/-0.5°C from -10°C to +85°C
0-100% RH +/- 1.8%
Xytronix Research & Design, Inc.
Page 149
Содержание X-600M
Страница 1: ...X 600MTitle Page Goes Here...
Страница 6: ...X 600M Users Manual Page 4 Xytronix Research Design Inc...
Страница 99: ...X 600M Users Manual Setup Pages Xytronix Research Design Inc Page 97...
Страница 116: ...Appendix B Installing New Firmware X 600M Users Manual Page 114 Xytronix Research Design Inc...