Mechanical
Installation
Electrical
Installation
Getting
Started
Menu 0
Running
the motor
Optimisation
Macros
Advanced
Parameters
Technical
Data
Diagnostics
UL Listing
Information
54
Unidrive User Guide
www.controltechniques.com Issue Number: 9
4.9.3 Unidrive VTC control terminal default
configuration
The following is a list of the terminal default functions for Unidrive VTC.
Any terminal not listed has the same default function as Unidrive.
4.10 Encoder connections
4.10.1 Quadrature encoder connections
Figure 4-17 Encoder connections (default configurations)
For encoder cable screening, see section 4-10
Descriptions of the encoder connections
30
Drive enable input F7
OL> EXTERNAL TRIP INPUT
CL> DRIVE ENABLE input
Type
Negative or positive logic digital inputs
Logic mode controlled by...
Parameter
8.27
Voltage range
0V to +24V
Absolute maximum
voltage range
–3V to +30V
Input current when 0V applied
≥
3.2mA
Negative-logic levels
Inactive state (input open-circuit):
>+15V
Active state: <+5V
Positive-logic levels
Inactive state (input open-circuit): <+5V
Active state: >+15V
Sample period
Enable function
PWM switching frequency dependent
5.5ms for 3, 6, & 12kHz
7.4ms for 4.5 & 9kHz
Disable or trip function
1ms
31
0V common (digital)
Function
Common connection for external digital
devices.
5
Analog input 1
±10V frequency reference input
6
(differential input)
7
Analog input 2
EUR> ±10V frequency reference
input
USA> 4 to 20 mA frequency
reference input
8
Analog input 3
Motor thermistor input (PTC)
9
Analog output 1
Frequency output
10
Analog output 2
Total motor current output
24
Digital input / Output F1
EUR> AT SPEED output
USA> DRIVE RUNNING output
25
Digital input / Output F2 RESET input
26
Digital input / Output F3 PRESET SELECT
27
Digital input F4
EUR> RUN FORWARD input
USA> RUN input
28
Digital input F5
EUR> RUN FORWARD input
USA> ANALOG INPUT 1 / INPUT
2 SELECT input
29
Digital input F6
ANALOG INPUT / PRESET REF
SELECT input
1
Quadrature channel A
2
Quadrature channel A\
3
Quadrature channel B
4
Quadrature channel B\
5
Marker pulse channel Z
6
Marker pulse channel Z\
Type
EIA422 differential receivers
Maximum data rate
250kHz (equivalent of 3,000rpm with a
5,000 lines per revolution encoder)
Line termination components
120
Ω
(switchable using Pr
3.24
)
Line loading
1 unit load
Absolute maximum applied voltage
relative to 0V
±
15V
Absolute maximum applied differential
voltage
±
25V
Encoder connector
Female 15-way D-type
Encoder
Commutation
signal
connections for
servo-encoders
only
Incremental
signal
connections for
all encoders