![Control Techniques Unidrive 1 Series Скачать руководство пользователя страница 53](http://html.mh-extra.com/html/control-techniques/unidrive-1-series/unidrive-1-series_user-manual_2658692053.webp)
Safety
Information
Product
Information
Mechanical
Installation
Electrical
Installation
Getting
Started
Menu 0
Running
the motor
Optimisation
Macros
Advanced
Parameters
Technical
Data
Diagnostics
UL Listing
Information
Unidrive User Guide
53
Issue Number: 9 www.controltechniques.com
The default configuration of the above digital inputs and outputs are
different for Unidrive VTC. See Figure 4-16
terminal functions (European and USA)
Unidrive VTC control terminal default configuration
details.
9
Analog output 1
OL> FREQUENCY output signal
CL> SPEED output signal
10
Analog output 2
TORQUE output signal
Type of output
Bipolar single-ended analog voltage or
unipolar current output
Mode controlled by...
7.19
&
7.22
Operating in Voltage mode
Output voltage range
±
10V
Maximum output current
10mA peak
Load resistance
1k
Ω
minimum
Protection
Short-circuit proof
Operating in current mode
Current ranges
0 to 20mA
4 to 20mA
Maximum output voltage
±
12V
Maximum load resistance
600
Ω
Equivalent input resistance
≤
200
Ω
at 20mA
Common to all modes
Resolution
10-bit plus sign
Update period
PWM switching frequency dependent
5.5ms for 3, 6, & 12kHz
7.4ms for 4.5 & 9kHz
11
0V common (analog)
Function
Common connection for external
analog devices.
21
0V common (digital)
22
+24V digital supply
Function
Supply for external digital signal
devices
Voltage tolerance
±
10%
Nominal output current
200mA (total including any digital
outputs)
Overload output current
240mA (total including any digital
outputs)
Protection
Current foldback above 240mA
23
0V common (digital)
Function
Common connection for external digital
devices.
24
Digital input / output F1
OL> AT-SPEED output
CL> AT ZERO SPEED output
25
Digital input / output F2 RESET input
26
Digital input / output F3 JOG SELECT input
Type of output
Negative or positive logic digital inputs,
or
negative-logic push-pull or open
collector digital outputs
Input / output mode controlled by...
Parameters
8.12
,
8.15
&
8.18
Operating as an input
Logic mode controlled by...
Parameter
8.27
Absolute maximum voltage range
-3V to +30V
Input current when 0V applied
≥
3.2mA
Negative-logic levels
Inactive state (input open-circuit):
>+15V
Active state: <+5V
Positive-logic levels
Inactive state (input open-circuit): >+5V
Active state: <+15V
Operating as an output
Open collector outputs selected by...
Parameter
8.28
Maximum output current
200mA (total including terminal 22)
Overload output current
240mA (total including terminal 22)
Common to both modes
Voltage range
0V to +24V
Sample / Update period
PWM switching frequency dependent
5.5ms for 3, 6, & 12kHz
7.4ms for 4.5 & 9kHz
27
Digital input F4
RUN FORWARD input
28
Digital input F5
RUN REVERSE input
29
Digital input F6
ANALOG INPUT 1 / INPUT 2
SELECT INPUT
Type
Negative or positive logic digital inputs
Logic mode controlled by...
Parameter
8.27
Voltage range
0V to +24V
Absolute maximum
voltage range
–3V to +30V
Input current when 0V applied
≥
3.2mA
Negative-logic levels
Inactive state (input open-circuit):
>+15V
Active state: <+5V
Positive-logic levels
Inactive state (input open-circuit): <+5V
Active state: >+15V
Sample period
PWM switching frequency dependent
5.5ms for 3, 6, & 12kHz
7.4ms for 4.5 & 9kHz
Содержание Unidrive 1 Series