Over Current in braking transistor
4
Over current threshold in the braking transistor has been reached.
This can be caused by the following:
•
A short-circuit exists across the braking resistor terminals.
•
An insulation fault on the braking resistor or associated cables.
•
The ohmic value of the braking resistor is too low.
OI.dc n
DC over current trip in module n
134 to 141
DC instantaneous over current trip in module
n
(size 5 only)
OP.OVLd
Control terminals output overload
26
The total current drawn from the user +24V supply (terminal 22) and any digital outputs (terminals 24, 25 and 26) exceeds 240mA.
Ot HS n
Heatsink over temperature in module n
102 to 109
Heatsink over temperature threshold has been reached in module
n
(size 5 only); detected by one of the two thermistors in the drive.
Ensure that ventilation at the front and rear of the drive is adequate.
Check cubicle / drive fans are still functioning correctly.
Check cubicle ventilation paths.
Check cubicle door filters.
Increase ventilation.
Decrease acceleration / deceleration rates.
Reduce duty cycle.
Reduce motor load.
Ot inP
Input stage over temperature
101
Input stage over temperature threshold has been reached (size 5 only).
Ensure that ventilation at the front and rear of the drive is adequate.
Check cubicle / drive fans are still functioning correctly.
Check cubicle ventilation paths.
Check cubicle door filters.
Increase ventilation.
Decrease acceleration / deceleration rates.
Reduce duty cycle.
Reduce motor load.
OU
Over Volts on the DC bus
2
Over voltage threshold on the DC bus has been reached.
400V Unidrive: >830Vdc
200V Unidrive LV: >415Vdc
This is due to excessive AC supply voltage or excessive regenerated power being returned to the drive that can be caused by the
following:
•
Pr
0.04
Deceleration rate
set too low.
•
An external force acting on the motor shaft causing the drive to regenerate.
•
Braking resistor value is too high.
•
AC supply voltage too high.
•
Supply disturbance such as a voltage over-shoot as the supply recovers from a notch induced by a DC drive.
•
Motor insulation fault.
OU n
Over volts on the DC bus in module n
126 to 133
Over voltage threshold on the DC bus of module
n
of 830Vdc, has been reached (size 5 only). (The FLC of the drive is displayed in
Pr
11.32
)
This is due to excessive regenerated power being returned to the drive that can be caused by the following:
•
Pr
0.04
Deceleration rate
set too low.
•
An external force acting on the motor shaft causing the drive to regenerate.
•
Braking resistor value is too high.
•
AC supply voltage too high.
•
Supply disturbance such as a voltage over-shoot as the supply recovers from a notch induced by a DC drive.
•
Motor insulation fault.
OU.SPd
Over speed
7
The motor speed has reached the over speed threshold (Pr
3.08
).
This can be caused by the following:
•
Sudden removal of a large mechanical load from the motor shaft.
•
Pr
0.04
Deceleration rate
set too low.
•
Inappropriate setting for Pr
0.16
Stop mode selector.
•
Pr
0.19
S-ramp da/dt
set too high.
•
Pr
3.08
set below the maximum reference obtainable, i.e. set less than Pr
0.02
(or Pr
1.06
).
•
Speed over-shoot due to high speed loop proportional gain (Pr
3.10
)
Trip
Diagnosis