![Control Techniques UD77 DeviceNet Скачать руководство пользователя страница 56](http://html1.mh-extra.com/html/control-techniques/ud77-devicenet/ud77-devicenet_user-manual_2658684056.webp)
56 Issue
Number:
2
10.5 Unidrive
Trip
Codes
The trip codes listed below may be caused by the Unidrive DeviceNet
interface. Other trips may occur if a DPL program is loaded. For a full
list of UD70 trips, refer to the UD70 User Guide
Trip
Code
Error
tr52
This code indicates that the trip originated from the setting of
bit 4 in the control Word
tr56
The UD70 does not contain the correct operating system for
the detected hardware. Download the system file
“IBSPROFI.SYS”. If the trip persists, ensure that the UD73A
and UD70 boards inside the module are properly clipped
together. (This should only be attempted by suitably qualified
personnel!!)
tr57
An illegal operating system call has been made, e.g. WRNET.
CTNet commands cannot be used with DeviceNet
tr60
Bus Off. This is a low-level CAN trip condition, and prevents
the node from communicating with the network. A manual
reset is required to clear the Bus Off condition
tr62
This trip indicates that loss of the DeviceNet network has been
detected. This can be caused by disconnecting the node from
the network, a bad cable connection, or by resetting or
stopping the network master controller