![Control Techniques UD77 DeviceNet Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/control-techniques/ud77-devicenet/ud77-devicenet_user-manual_2658684011.webp)
Issue Number: 2
11
3.5 DeviceNet
Network
Termination
There is no termination resistor supplied on the Unidrive DeviceNet
interface. It is the user’s responsibility to ensure that both ends of each
section of network cable are correctly terminated.
A 120
Ω
0.25W resistor should be connected between the CAN_H and
CAN_L lines at each end of the main trunk cable, as shown in the
diagram below.
CAN-L
CAN-H
0V
+24V
Shield
1 2 3 4 5
Fit 120W 0.25W network
termination resistor between
CAN-L and CAN-H
0V
+24V
CAN-L
CAN-H
NOTE
The above method of connecting the termination resistor ensures that
the network remains terminated when the DeviceNet connector is
disconnected from the node.
It is very important in high-speed communications networks that the
network communications cable is correctly terminated. Failure to
terminate the network properly may mean that the network operates
with substantially reduced noise immunity, or in the worst case, the
network doesn’t work at all.