![Control Techniques UD77 DeviceNet Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/control-techniques/ud77-devicenet/ud77-devicenet_user-manual_2658684021.webp)
Issue Number: 2
21
5.7 Fieldbus
Control
Word
for
Unidrive
NOTE
This section assumes that the Unidrive is configured to use the
default Wire Proof PLC sequencing mode (#6.04 = 4). If PLC mode is
selected (#6.04 = 3), the control word mapping is slightly different.
Refer to section 9.2 for details.
The Control Word is an efficient way of remotely controlling the motion
of a Unidrive. Each bit in the control word has a particular function, and
provides a method of controlling the function of the Unidrive (RUN,
JOG, etc.) with a single data word. The control word is addressed in
the UD70 by writing to #90.11.
b15 b14 b13 B12 b11 b10 b9
b8
M6 M5
#18.33
M3 M2 M1 M0 #18.32
b7 b6 b5 b4 b3 b2 b1 b0
#18.31 #1.46 #1.45 TRIP RUN
REV
JOG RUN
FWD
ENABLE
The bits shown as “Mx” are individual mask bits that allow the
corresponding "bx” to be masked, i.e. the MASK bits determine whether
or not the data bit is written through to the corresponding parameter.
#6.15
#6.30
#6.31
#6.32
b0
b1
b2
b3
b4
b5
b6
b7
b8
MO
M1
M2
M3
b13
M5
M6
1
1
0
0
1
0
#1.47
Trip
#1.46
#18.33
#18.32
#18.31
1
0
1
0
1
0
If mask bits M0 and M1 are set to 1, ENABLE and RUN FWD are
updated with the values of b0 and b1 (either 0 or 1) every time the
control word value is received. JOG and RUN REV will not be updated,
even if the values of b2 and b3 change, because their mask bits (M2
and M3) are not set to 1. If M0 and M1 are reset to 0, the values in b0
and b1 will NOT be written to ENABLE and RUN FWD, and these
parameters will remain set to their current state.