46 Issue
Number:
2
9.11.6 Ready
Class: 41 (0x29)
Instance: 1 (0x1)
Attribute: 9 (0x9)
Read only attribute that indicates that the drive is enabled and ready to
run.
Action Mapping
Read #6.15
9.11.7 Faulted
Class: 41 (0x29)
Instance: 1 (0x1)
Attribute: 10 (0xA)
Read only attribute that indicates that the drive tripped when set to 1.
Action Mapping
Read !#10.01
NOTE
This is the opposite polarity to #10.01 on the Unidrive.
9.11.8 FaultRst
Class: 41 (0x29)
Instance: 1 (0x1)
Attribute: 12 (0xC)
Set to 1 to reset a drive from a tripped condition. Note that with
Unidrive, this will cause a complete reset of the DeviceNet interface.
Action Mapping
Write (0)
No action
Write (1)
#10.38 = 100
9.11.9 FaultCode
Class: 41 (0x29)
Instance: 1 (0x1)
Attribute: 13 (0xD)
Returns a fault code number, indicating the reason why the drive
tripped. Refer to the Unidrive or Mentor II User’s Guides for a full list of
fault codes.
Action Mapping
Read #10.20
Under normal operating conditions, the Unidrive and Mentor II will be in
the “Drive Healthy” condition, indicating that the drives are operating
with no problems. This condition is indicated by a value of 1 in #10.01
on Unidrive.
If a drive trips for any reason, the drive healthy bit is reset to 0, and a
diagnostic code is provided to indicate the reason for the trip. This code
is available from #10.20 in the Unidrive.