SM-Encoder Plus & SM-Encoder Output Plus User Guide
www.controltechniques.com
Issue: 4
8
Terminal data
8.1
Encoder inputs (PL1)
Ab, Fd, and Fr encoders
8.1.1
SM-Encoder Plus
8.1.2
SM-Encoder Output Plus
The encoder supply voltage is controlled by Pr
x.13
. The default for this parameter is 5V
(0) but this can be set to 8V (1) or 15V (2). Setting the encoder voltage supply too high
for the encoder could result in damage to the feedback device.
The termination resistors should be disabled (Pr
x.16
= 0) if the outputs from the
encoder are higher than 5V.
1
Channel A, Frequency or Forward inputs
2
Channel A\, Frequency\ or Forward\ inputs
3
Channel B, Direction or Reverse inputs
4
Channel B\, Direction\ or Reverse\ inputs
5
Marker pulse channel Z
6
Marker pulse channel Z\
Type
EIA 485 differential receivers
Maximum frequency
500kHz
Line loading
<2 unit loads
Line termination components
120
Ω
Working common mode range
+12Vdc to –7Vdc
Absolute maximum applied voltage relative to
0V
±
25V
Absolute maximum applied differential voltage
±
25V
7
0V Common
8
External power supply decoupling
Maximum voltage
±
50Vdc
8
Encoder supply voltage
Supply voltage
5V, 8V or 15V
Maximum output current
300mA for 5V and 8V
200mA for 15V