18
SM-Encoder Plus & SM-Encoder Output Plus User Guide
www.controltechniques.com
Issue: 4
5.2
Incremental set-up
The following parameter set-up should be followed when operating with an Incremental Encoder
Incremental encoders, Ab, Fd and Fr
Action
Detail
Before power-up
Ensure:
•
Drive SECURE DISABLE/SAFE TORQUE OFF is not given (terminal 31)
•
Run signal is not given
•
Solutions Module is fitted in appropriate slot
•
Feedback device is connected
Power up drive
Ensure:
•
Drive displays ‘inh’
If the drive trips see Chapter 7
Error detection
Ensure:
•
If no encoder is connected the encoder input on the drive then Pr
3.40
should be
set to 0 to disable the drive encoder input wire break detection (Enc2 trip).
Slot identification
Identify which Solutions Module slot and menu are being used
•
Slot 1 – Menu 15
•
Slot 2 – Menu 16
•
Slot 3 – Menu 17
Select Solutions
Module
Enter:
•
Speed feedback selector Pr
3.26
1: Slot 1
2: Slot 2
3: Slot 3
Set-up encoder power
supply (SM-Encoder
Output Plus only)
Enter:·
•
Encoder power supply Pr
x.13
.
0
: 5V,
1
: 8V,
2
: 15V
Set-up encoder
parameters
Enter:
•
Encoder type Pr
x.15
0
(Ab)
1
(Fd)
2
(Fr)
Set-up encoder lines
per revolution
•
Equivalent lines per revolution Pr
x.10
Set according to encoder, see below for restrictions
Initialisation
Ensure:
Position feedback is initialised Pr
x.45
Encoder
Pr x.10 Equivalent lines per revolution
Ab
Number of lines per revolution
Fd, Fr
Number of lines per revolution / 2