14
SM-Encoder Plus & SM-Encoder Output Plus User Guide
www.controltechniques.com
Issue: 4
Figure 4-6 Encoder galvanically isolated from encoder body
4.3.3
No isolation
As shown in Figure 4-7 the encoder 0V connection may be permanently connected to
the housing. This has the advantage that the encoder body can form a shield for its
internal circuits. However it permits noise current from the motor body to flow into the
encoder cable shield. A good quality shielded cable correctly terminated protects the
data against this noise current, but much more care is needed in ensuring correct cable
management than for the isolated cases.
Figure 4-7 No isolation