59
M’Ax Advanced User Guide
www.controltechniques.com
Issue Number: 4
A 0 to 1 change on this parameter will cause a drive reset. If a drive reset terminal is required on the drive the required terminal must be
programmed to control this bit. Digital input 6 is defaulted to reset function.
No.
String
Cause of trip
1
UU
DC link under voltage
2
OU
DC link over voltage. This could be because the DC link voltage has exceeded the maximum level
or has remained above the maximum continuous level for more than 30s.
Drive voltage rating: 400V
Instantaneous trip: 830V
Max continuous level: 810V
3
OI.AC
AC instantaneous over current, caused by hardware fault, this trip cannot be reset for 2s
4
OI.br
Braking resistor instantaneous current trip. This trip cannot be reset for 2s.
5
PS
Internal drive power supply trip
6
Et
External trip
7
OU.SPd
Over speed (see [3.08])
8 ~ 10
tr08 ~ tr10
User trips
11
tunE1
No axis movement, during Flux alignment procedure.
12
tunE2
Incorrect direction of rotation, during Flux alignment procedure
13 ~ 17
tr13 ~ tr17
User trips
18
tunE
Flux alignment procedure stops before completion
19
It.br
Braking resistor over-heat based on thermal model. (see [10.39])
20
I2t.AC
Motor over-heat based on thermal model (see [10.58])
21
O.ht1
Drive over-heat based on thermal model (see [10.56])
22
O.ht2
Drive over-heat based on heat sink temperature (see [7.04])
23
O.ht3
SLM over-heat based on PCB temperature (see [10.59])
24
O.ht4
SLM over-heat based on PCB temperature (see [10.59])
25
tr25
User trips
26
OP.Oul
Digital output overload
27 ~ 29
tr27 ~ tr29
User trips
31
EEF
Internal drive EEPROM failure. All the parameters are set to default. The trip can only be removed
by entering a load default command (i.e. 1233,1244,1255 etc.) into parameter [x.00] before
resetting the drive.
32
Ph
High input voltage phase imbalance or input phase loss. Normally a motor load of between 50 and
100% or drive rating is required to trigger the trip. The drive will attempt to stop the motor before
tripping, if specified in parameter [10.54].
33 ~ 49
tr33 ~ tr49
User trips
50
dL.Er
DrivelinK hardware error. Possibly due to:
•
No 24v supply to SLM
•
Faulty cable
•
Damaged SLM / drive RS485 drivers due to excessive ESD
51
dR.SI
Motor / drive excessive current rating mismatch
52
SL.Er
See parameter 10.52 for explanation
53
CtC.Er
Encoder error cause:
•
Quadrant mismatch
•
Initialisation failure
54
SL.Er
The SLM is being initialised (the trip code is seen momentarily when the drive is being powered-
up). Momentary display of the trip code does not cause the drive to trip.
55
In.An9
Initial mismatch from the SLM; contact the supplier of the drive.
56 ~ 99
tr56 ~ tr99
User trips
100
tr100
Drive reset
101 ~ 254 tr101 ~ tr254 User trips
255
tr255
Clear trip log information
10.33
Drive Reset
ô
0 ~ 1
ð
RO
Bit
Содержание M'Ax
Страница 9: ... M Ax Advanced User Guide 6 Issue Number 4 www controltechniques com ...
Страница 47: ... M Ax Advanced User Guide 44 Issue Number 4 www controltechniques com ...
Страница 48: ... 45 M Ax Advanced User Guide www controltechniques com Issue Number 4 Figure 9 1 Menu 7 software diagram ...
Страница 49: ... M Ax Advanced User Guide 46 Issue Number 4 www controltechniques com ...
Страница 73: ... M Ax Advanced User Guide 70 Issue Number 4 www controltechniques com ...