M’Ax Advanced User Guide
40
Issue Number: 4
www.controltechniques.com
Only one stopping phase exists and the ready state is entered as soon as the single stopping action is complete.
0 = Disabled
There is no mains loss detection and the drive operates normally as long as the DC Link voltage within specification
i.e greater than DC Bus undervolt trip level.
1= Controlled Stop
The drive detects mains loss by comparing the DC bus voltage with the controlled stop enable DC bus level parameter [6.48]. If the DC bus
level is less than the value stored in parameter [6.48] then a controlled stop is requested, which triggers a controller to operate. This controller
will regulate the ramp rate to keep the DC bus level above the programmed level as close as possible to the required ramp rate. Controller
gains can be adjusted using parameters [2.46] & [2.47].
The drive will continue a controlled stop even if mains voltage is restored, a drive reset is necessary to resume normal application. During a
controlled stop the drive will display “CSP”.
When this bit is set the drive will hold torque at standstill when not in the running state rather than disabling the output bridge. The drive status
will be StP when the drive is at standstill rather than rdY.
0 = rdY
1 = StP
Setting this parameter to 0 will disable the drive. It must be at 1 for the drive to run.
0 = Drive disable
1 = Drive enable
Hardware enable contact must also be closed to run the drive. Refer to parameter 8.09 for hardware enable indicator.
Together with the next parameter the drive records the amount of time the drive has been running since it left the manufacturing plant.
Together with the previous parameter the drive records the amount of time the drive has been running since it left the manufacturing plant.
The drive sequencer uses these bits as inputs rather than looking at terminals directly. This allows the customer to define the use of each
drive terminal according to each application needs.
0 = Disabled
1 = Enabled
6.01
Stop mode selector
ô
0 ~ 2
ð
2
RW
Txt
P
Stopping
Mode
Action
0 - COASt
Inhibits the inverter
1 - rP
Stop with ramp
2 - no.rP
Stop with no ramp
6.03
AC supply loss mode selector
ô
0 ~ 1
ð
0
RW
Bit
P
6.08
Hold zero speed select
ô
0 ~ 1
ð
1
RW
Bit
6.15
Drive enable
ô
0 ~ 1
ð
1
RW
Bit
6.20
Power-up time (Years, Days)
ô
00.00 ~ 9.365
ð
Yrs ~ days
RO
Uni
S
P
6.21
Power-up time (Hours, Minutes)
ô
00.00 ~ 23.59
ð
Hours ~ Mins
RO
Uni
S
P
6.31
Sequencing Bit JOG FORWARD
6.32
Sequencing Bit JOG REVERSE
6.33
Sequencing Bit FORWARD / REVERSE
6.34
Sequencing Bit RUN
ô
0 ~ 1
ð
0
RW
Bit
NOTE
Содержание M'Ax
Страница 9: ... M Ax Advanced User Guide 6 Issue Number 4 www controltechniques com ...
Страница 47: ... M Ax Advanced User Guide 44 Issue Number 4 www controltechniques com ...
Страница 48: ... 45 M Ax Advanced User Guide www controltechniques com Issue Number 4 Figure 9 1 Menu 7 software diagram ...
Страница 49: ... M Ax Advanced User Guide 46 Issue Number 4 www controltechniques com ...
Страница 73: ... M Ax Advanced User Guide 70 Issue Number 4 www controltechniques com ...