Description of application and parameters
Application program
29
NOTE
This parameter is only visible if the "Use of a two-stage switch-off" parameter is
set on "Yes".
Options:
00:00:10 .. 00:05:00 .. 18:12:15
– Here the value for the switch-off delay of the reduced brightness is set. The total switch-off
delay then consists of the switch-off delay + brightness reduced according to switch-off
delay.
Options:
No
Yes
–
No
: The detector does not switch off after a specific time to carry out a new brightness
measurement.
–
Yes
: The detector switches off once after 3x switch-off delay or at a minimum of 90 minutes
or a maximum of 24 hours to carry out a new brightness measurement.
If the presence detector is switched on, it operates independent of brightness. Problem: When
movement is detected the light remains on even though the brightness may be sufficient. This
effect can be prevented by activating this parameter.
Options:
No
Yes
–
No
: The only option available is to change the switch-off delay via the switch-off delay
parameter setting.
–
Yes
: There is a separate 2-byte switch-off delay object (input) for changing the switch-off
delay of the detector. The time entered is in seconds. A switch-off delay of 4 minutes, for
example, has a value of 240 seconds.
NOTE
The values which can be sent are between 10 and 65535 seconds. If a value
that is too small or too large is sent, the value is automatically adjusted to the
limit value:
■
Value < 10 -> Value = 10
■
Value < 65535 -> Value = 65535