Description of application and parameters
Application program
27
Options:
Automatic mode
Automatic switch-off
Automatic switch-on
Surveillance
–
Automatic
= automatic switch-on and switch-off.
The detector switches on automatically when detecting a movement. The switch-off is
effected after the set switch-off delay beginning from the most recent detection.
–
Automatic switch-off
: Manual switch-on and automatic switch-off.
The detector must be switched on manually via object "External push-button (input)". The
switch-off is effected automatically under consideration of the switch-off delay.
–
Automatic switch-on
: Automatic switch-on and manual switch-off.
The detector switches on automatically when detecting a movement. The switch-off is
effected by the receipt of an Off telegram on object "External push-button (input)". Note: The
detector switches off automatically after 6 hours.
–
Surveillance
: Automatic switch-on and switch-off.
The detector switches on brightness-dependent if an adjustable component of movement
has been recorded within the time period set. The switch-off occurs 2 seconds after switch-
on and the last detection of movement.
NOTE
Manual switch-on and switch-off is possible in operating modes automatic,
automatic switch-on and automatic switch-off via the external push-button
(input). This external push-button is activated under the "External push-button"
parameter. During manual switch-off the detection of movement is suppressed
for the pause time. The purpose of pause time is to prevent an immediate re-
activation.
Example:
The person switches the light off manually when leaving the room. Without the
pause time the detected movement would cause a renewed switch-on during
exiting.