Instrument Calibration
42
515 HC04 - 8 June 2007
TYPE
ALRM
n
The options available for alarm types are as follows:
•
HI-NO — High Alarm, Normally Open contacts
•
HI-NC — High Alarm, Normally Closed contacts
•
LO-NO — Low Alarm, Normally Open contacts
•
LO-NC — Low Alarm, Normally Closed contacts
•
BD-NO — Band Alarm, Normally Open contacts
•
BD-NC — Band Alarm, Normally Closed contacts
•
AL-NO — Equipment Alarm, Normally Open contacts
•
AL-NC — Equipment Alarm, Normally Closed contacts
Press
or
to select the type of alarm required.
POINT
ALRM
n The Alarm Setpoint is available for viewing and editing for any alarm
type except ‘equipment alarms’
.
The Alarm Setpoint is the value (in engineering units of assigned
variable) at which the alarm condition occurs and therefore the alarm is
on.
Each alarm is completely independent, e.g. a High alarm does NOT need
to have a higher setpoint than the a Low alarm.
HYST
ALRM
n The Alarm Hysteresis is available for viewing and editing for any alarm
type except ‘equipment alarms’
.
Alarm hysteresis loops occur when the alarm toggles continuously on and
off when the process variable is close to the setpoint.
For a high alarm, the alarm activates when the value of the variable rises
above the alarm setpoint and deactivates when the value falls below the
alarm setpoint minus the amount of the hysteresis setting (if any).
For a low alarm, the alarm activates when the value of the variable falls
below the alarm setpoint and deactivates when the value rises above the
alarm setpoint plus the amount of the hysteresis setting (if any).
For a band alarm, the alarm activates whenever the value of the variable
is outside the setpoint plus or minus the amount of the hysteresis.
For example, with a high alarm setpoint of 200, and a hysteresis setting
of zero, a value oscillating between 197 and 202 will cause the alarm to
toggle on at 200 and toggle off below 200. However, if the hysteresis is
set to 5, the value of the variable must fall below 195 to cancel the alarm.
The alarm will reactivate only when the value again rises above 200.
↓
→
UNITS PARAMS INPUTS OUTPUTS
ALARMS
COMMS TM/LOG SETUP TEST END
SET
Содержание 515
Страница 4: ...iv 515 HC04 8 June 2007 ...
Страница 8: ...viii 515 HC04 8 June 2007 ...
Страница 16: ...Introduction 8 515 HC04 8 June 2007 ...
Страница 60: ...Instrument Calibration 52 515 HC04 8 June 2007 ...
Страница 80: ...Communications 72 515 HC04 8 June 2007 ...
Страница 82: ...74 515 HC04 8 June 2007 ...
Страница 88: ...80 515 HC04 8 June 2007 ...