Instrument Calibration
515 HC04 - 8 June 2007
39
Outputs
PT-MIN
AINP1
PT-MAX
PT-MIN
AINP2
PT-MAX
The Minimum Point and Maximum Point parameters are only for 0-5V,
1-5V and 4-20mA inputs.
Enter the value of the measured parameter that corresponds to the
minimum input signal level. The minimum point is commonly referred to
as the base value.
Enter the value of the measured parameter that corresponds to the
maximum input signal level. The maximum point is the same as the base
value (set at the minimum point) plus the span value.
For example, if the source signal is 4mA for a temperature of 10°C, enter
10 for the minimum point. If the source signal is 20mA for a temperature
of 2000°C, enter 2000 as the maximum point.
EXCEPT
DEFLT
If Default Value On Exception is enabled the instrument will use the
default value for the analog input that raised the exception. This will
allow calculations to continue, however the exception message will
continue to be displayed until the error is rectified or the input type is set
to DEFAULT in calibration set mode.
Press
or
to select ENABLE or DISABLE.
↓
→
UNITS PARAMS
INPUTS
OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
SET
↓
→
UNITS PARAMS INPUTS
OUTPUTS
ALARMS COMMS TM/LOG SETUP TEST END
PULSE
OUT
n
or
4-20
You can assign any of the “main menu” variables to an output. The nature
of the output depends on the assigned variable. Totals are output as pulses
and rates are output as 4-20mA passive signals.
Press
or
to select the variable that is required as an output. The
top of the display shows the type of output signal that is assigned to the
variable.
CAUTION
Due to the dual-purpose nature of the outputs, take care not to
set the output as an open collector pulse type signal when
connected to a 4-20mA loop circuit.
WIDTH
OUT
n The Output Pulse Width is available for viewing and editing only when
the assigned variable is a total (pulse output) type.
Pulse output is usually used to drive remote counters. Set the pulse width
(in milliseconds) as required by the remote counter.
Press
or
to set to: 10, 20, 50, 100, 200 or 500ms.
SET
Содержание 515
Страница 4: ...iv 515 HC04 8 June 2007 ...
Страница 8: ...viii 515 HC04 8 June 2007 ...
Страница 16: ...Introduction 8 515 HC04 8 June 2007 ...
Страница 60: ...Instrument Calibration 52 515 HC04 8 June 2007 ...
Страница 80: ...Communications 72 515 HC04 8 June 2007 ...
Страница 82: ...74 515 HC04 8 June 2007 ...
Страница 88: ...80 515 HC04 8 June 2007 ...