ARCHITECTURAL AND ENGINEERING SPECIFICATION, v 2.7
44
6.
Local and Global Activity linking:
The system shall support both local (within
the same Access Control Panel) as well as global (spanning multiple Access
Control Panels) Activity linking for maximum system flexibility.
RR.
Alarm Event Limit:
1. This feature shall allow the user to limit the number of repeat alarm events sent
from a panel within a given period of time.
a. The user shall have the ability to add a time delay on an alarm to
lessen the number of alarms that will be sent to the Pending Alerts grid
for an input that remains ‘Abnormal’.
b. This time delay setting shall be configurable and shall be in minutes.
SS.
Variable Door Open/Shunt Time:
1. This feature shall allow the user to unlock a door, either through Manual control
or a card read, for a period as short as one second or up to one hour.
a. The system shall bypass the door input for the same time as the
unlock time.
b. The system shall allow for time increments in seconds up to 59 and
then in minutes only up to 60.
c. The system shall allow for the same manual control over relays.
TT.
Application Programming Interface:
1. The system shall provide for an Application Programming Interface for third party
integration.
2. The API shall be constructed as a standard Windows Dynamic Link Library (DLL)
and will provide various functionalities in the form of function calls.
UU.
Right-to-Left Language Support:
1. The system shall support Languages requiring a display from right-to-left
including, but not limited to, Arabic and Hebrew.
VV.
Access Control Panels:
Continental Access Control Panels used by CardAccess
3000 are modular in design. The access control panels (or panels for short) are also
referred to as controllers. Two door, four door and eight door panel versions are
available.
1.
General Features:
a.
PC Board:
The Access Control Panel shall be a microprocessor
controlled solid-state electronic device and will include a real time
clock/calendar on board. The Access Control Panel shall be compliant
with UL294, or an equal. A subset of the ACS database sufficient
enough to support access and alarm functions for its designated