ARCHITECTURAL AND ENGINEERING SPECIFICATION, v 2.7
17
3. The database will fully integrate with the Government PKI database for validation
of a card and automatically remove access privileges when the card holder
information is moved to the Government Revocation list.
M.
Access Control Panel:
The Access Control Panel system shall be scalable and operate
efficiently over a wide range of facility sizes and applications. Systems utilizing a remote
module at the door that reports back to the controller will not be accepted. The Access
Control Panels shall be capable of:
1. Entry/exit points will be able to be added without the need to replace any system
hardware or controllers.
2. Controllers may be selected and added in increments of 1, 2, 4 and 8 door
configurations to provide the maximum flexibility and cost effectiveness.
3. Distributed, intelligent, fully independent controllers will be able to be used to
provide fully distributed decision and authorization capabilities.
4. In the event the host PC cannot communicate with any/all controllers, no
degradation in security shall occur.
5. Reading multiple cards formats simultaneously with no degradation of “time to
unlock”
6. Multiple reader formats/readers shall be read at a single controller
simultaneously
7. Reading bit structures from 26 bit to 256 bits
8. Storing up to 1,000,000 card holder records
9. Reading the FIPS-201-1, PIV, TWIC and CAC card formats
10. Shall be capable of Time Zone Offsets for those panels deployed in different time
zones.
11. Unlock times not to exceed .5 seconds after a valid card read
12. Download speeds to be at 921 kbps allowing for 40,000 cards to be downloaded
in less than two minutes.
2.4. SOFTWARE CAPACITIES
A. System software and language development software exist, and are industry accepted,
allowing the customer to choose the Language desired by the user. There can be full
customization of the Software GUI Screens, Icons, Communication messages, and
Reports. The Operating system shall be 32 bit multi-user / multi-tasking capable of
operating in a non-proprietary CPU. The application software shall be written in a
standard, industry accepted language. All System functions shall be accessible via
Microsoft Windows
®
XP Professional compliant menu-accessed screens. Systems
requiring command string control or complex syntax will not be acceptable. Systems shall
not be dependent upon external input, other than keyboard.
B. Each system shall be capable of supporting:
1. Over 2000 Serial/LAN Communication Ports and over 4000 Ports Total
2. Over 32,000 Readers
3. Unlimited Cardholder database (SQL Version-limited only to Hard drive capacity)
4. 150 Workstations
5. 255 Time Schedules each w/least 10 start/stop intervals
6. 5 Holiday types with 100 user-definable holidays each (500 Total)