Supplementary Heat Sources
If a supplementary heat source is connected to the storage tank the maximum energy input can be
not more that 10 kW including the electrical element. Where greater input is required, a pressure and
temperature relief valve with a higher kW rating is to be fitted to the storage tank.
Where stove coils are used for supplementary heating the water must be connected in an open
vented manner. Refer to Australian Standard AS3500 for more details on acceptable connection
solutions.
Any supplementary heat source must be limited such that the maximum tank temperature is 80 °C.
For the interconnecting details e.g. pipe work of your specific model/configurations please check the
assembly drawings in the following pages.
Common installation procedure
The roof system must be carefully inspected to ensure it can support the systems weight once it is
filled with water. Particular care must be taken where the front foot of the storage tank is located.
Typically the tank front foot should be located over a tile batten, purlin or similar for maximum
strength. If the roof can not support the load, additional bracing must be installed before the solar
water heater is installed.
Determining mounting location
The starting point for the installation is the storage tank front foot. The storage tanks front foot
must be located over a tile batten or purlin for maximum strength. The batten or purlin selected
must be located at least 2.4 metres up from the roof’s lower edge and 1 metres down from the
roof’s ridge line so that the ridge caps are not disturbed.
1.
2.
5.6.1
Place the tank into position with its front foot centrally over the selected tile batten. The tank
should be installed
after the collectors are installed. The tank centre should be installed over
rafters/trusses evenly so as to spread the tank weight over an even area of the roof.
Measure down the roof from the right side front edge of the front foot a distance of 2030 mm
and make a mark on the roof tile. This position (Point 2 of mounting location) will be the bottom
edge of the collector mounting rail.