11
.5
USB submenu
The control system must be equipped with a USB host port. This is located on the back of the control
board. The housing must be opened for this.
See Chapter 7.1.
The control system must be in operation in order to use this USB port.
Since the switch cabinet door is opened for this, it must be ensured that any danger from
electrical energy can be ruled out.
If necessary, live components should be covered.
The operator must also ensure that only qualified personnel are tasked.
We recommend using a USB-Y or USB extension cable between the control system and
the USB stick to connect the control system to the USB stick.
To load data from a USB stick to the control system or save from the device to the USB stick,
proceed as follows.
Open the control system and switch on the mains voltage. Insert a suitable USB stick into the
USB 2.0 host port. The control system provides acoustic confirmation if the USB stick has been
detected.
The USB menu is then opened in the main menu and the following functions are enabled by
pressing the symbol.
USB
Functions / explanations
Save the configuration to the stick
The data and setting parameters can be saved from the control system to the USB stick with this selection.
Read configuration from the stick
Data and setting parameters are loaded from the USB stick to the control system with this selection.
Make sure the data is compatible with the hardware.
Data from a 2-pump control system should not be loaded on a 1-pump control system, as this would cause
functional faults.
Save the operating data on the stick
The operating data (fault list, operating hours and switching cycles) can be saved on the USB stick in this
selection menu.
This data can then be opened and further processed in a spreadsheet application (MS Excel).
Software update from stick
If this function is selected, the control system searches for an update file on the USB stick.
If a suitable file is found, this is read from the control system after a prompt is confirmed, and the software is
updated.
This point is recommended when the manufacturer has made available a software update. The file
name of this software should not be changed.
Attention!
It is to be noted that the control system will automatically initiate the software update if the USB
stick is plugged in and the power turned on, without prompting the user!
Attention! After the data has been exchanged, remove the USB stick from the control
system! It should not remain plugged into the control system.
Switch off the mains voltage, remove the USB stick and close the control housing again.
Switch on the mains voltage.