Operating Instructions (GB)
900 191 - V1.0
_________________________________________________________________________________
Page 30
10.2.2
General pump-out settings
Function
Explanation
Pump-out run-on time
1 – 999 seconds
0 seconds > function off
After falling below the setpoint level, the pump remains in operation for
the set time.
Pump-out blocking time
1 – 999 seconds
0 seconds > function off
After the end of the pump-out process, it remains blocked for the set time.
Max. manual pump-out operation
1 – 120 seconds
0 seconds > function off
In this menu item the max. runtime for “Manual on” can be set for the
pump-out function.
See Chapter 7.8.
Max. runtime
1 - 9999 minutes.
0 minutes > function off
0000min Alarm: If the pump-out function runs longer than the entered
time without interruption, an alarm
Pump-out runtime
is triggered.
The pump(s) is (are) still in operation. If pumping-out is stopped, the
alarm will also stop.
0000min Stop: If the pump-out function runs longer than the entered time
without interruption, an alarm
Pump-out runtime
is triggered.
The pump(s) is (are) stopped. Pumping out does not continue until the
error has been manually acknowledged on the control system.
If pumps are not used for a longer period of time, they may be stuck the next time they are started.
A quick start for the pump(s) can be set in the following menu items. If the pumps have not been operated
during the set time, they are put into operation for the set number of seconds. An intermediate pumping
process resets the time counter.
Attention! If the water level falls below the minimum, this function will not be switched off.
Dry run of the pump(s) possible!
Quick start every...
1 – 9999 hours
0 hours > function off
Set the waiting time in hours after which the forced start-up is to take
place.
Quick start for...
1 – 9999 seconds
After the waiting time has elapsed, the pump(s) is (are) activated for the
set time.