56
1. Take the humidifier out of operation, as described in chapter 7.4.
2. Undo the brackets and open the right side panel(s).
3. Pull off the hose connected to the pressure switch (note the connection layout).
4. Remove the connection cable to the pressure switch (note assignment before removal).
5. Unscrew the two fixing screws and remove the air pressure switch.
Reinstallation follows in the reverse sequence. Make sure the cables and the hose are connected
correctly.
1. Take the humidifier out of operation, as described in chapter 7.4.
2. Undo the brackets and open the right front panel
3. Note the cable assignment, then remove all connection cables to the ignition module.
4. Unscrew the two fixing screws securing the ignition module and then remove ignition module.
Reinstallation follows in the reverse sequence. Make sure the connecting cables are connected correctly.
Replacement of the air pressure switch
Replacement of the ignition module