58
Replacing the auxiliary drain valve
1. Take the humidifier out of operation, as described in chapter 7.4.
2. Undo the brackets and open the right side panel.
3. Remove the connection cables to the auxiliary drain valve (note assignment before removal).
4. Disconnect the auxiliary drain valve from the tank connection and remove.
Reinstallation is carried out in the reverse sequence. Make sure the cables are connected correctly.
Replacing the fill valve
1. Take the humidifier out of operation, as described in chapter 7.4.
2. Undo the brackets and open the right side panel.
3. Remove the connection cables to the fill valve (note assignment before removal).
4. Remove hose clamps on the fill valve connections and pull off the hoses.
5. Undo the two screws fixing the fill valve to the housing, then remove the fill valve.
Reinstallation is carried out in the reverse sequence. Make sure the hoses are correctly secured with
the hose clamps and the cables are connected correctly.