8
Malfunctions
Important!
Most operational malfunctions are not caused by faulty equipment but rather by improper
installation or disregarding of planning guidelines. Therefore, a complete fault diagnosis always
involves a thorough examination of the entire system. Often, the steam hose connection has not
been properly executed, or the fault lies with the humidity control system.
8.1
Malfunction list
8.1.1
System faults
Warning
Error
Cause
Remedy
LED
Display
LED
Display
CP3 Card missing
(Test run possible)
CP3 Card missing
–––
Warning
W1: CP3 D-Card Missing
red
lights
Error
E1: CP-Card Missing
No CP3 Card installed on the control
board.
Install CP3 Card or start test run.
CP3 Card is empty
–––
–––
red
lights
Error
E2: CP-Card Empty
No data stored on the CP3 Card.
Install new CP3 Card.
CP3 Card is defective
–––
–––
red
lights
Error
E3: CP-Card Invalid
Invalid data stored on the CP3 Card.
Install new CP3 Card.
CP3 Card is incompatible
–––
–––
red
lights
Error
E4: CP-Card incompat
The installed CP3 Card is not compatible with
the hardware of the unit or with the basic
settings of the control electronics.
Install correct CP3 Card. Let your Condair
service technician adjust the basic
settings.
Wrong hardware settings
–––
–––
red
lights
Error
E9: Illegal Settings
False test run parameters.
Let your Condair service technician adjust
the test run parameters (heating voltage,
Cylinder-No.).
Hardware fault
–––
–––
red
lights
Error
E10: Flash R/W Fault
Control board defective.
Replace control board.
–––
–––
Error
E11: Clock R/W Fault
Backup battery on control board
discharged.
Let have the backup battery be replaced.
Maximum heating time reached
–––
–––
red
lights
Error
E13: Max.Heating
Maximum heating time is reached. Steam
generator was not switched off (manually
or by the timer).
Switch off steam generator when leaving
the steam bath cabin (with manual opera-
tion only).
Check timer settings (set heating time must
be shorter than the set maximum heating
time).
Increase maximum heating time.
Door of steam bath cabin open
–––
–––
red
lights
Error
E14: Door Open
Door of steam bath cabin has been open
too long, door switch has triggered.
Close door of steam bath cabin. Check door
switch, replace if necessary.
No cable bridge installed (in case that no
door switch is connected).
Install cable bridge (see wiring diagram).