Menu 1 – Pumps Setup
Pump Setup Screen
Figure 50 – Pump Setup Screen
Table 31 – Pump Setup Parameters
Menu Item
Description
Default
Value
Mode
AUTOMATIC: Allows for automatic timer enable of the pumps.
MANUAL: Requires manual enable of the pumps.
AUTOMATIC
Recirc On Delay
Delay duration before the Recirc Pump starts.
3 sec
Recirc Off Delay
Delay duration before stopping the Recirc Pump after initiation of a system stop.
60 sec
Process On Delay
Delay duration before the Process Pump starts.
30 sec
Process Off Delay
Delay duration before stopping the Process Pump after initiation of a system stop.
120 sec
VFD Pressure Setpoint
P1 Pump Pressure Setpoint (VFD OPTION ONLY)
50 PSI
Kp
Proportional PID value
100
Ti
Integral PID value
50
Td
Derivative PID value
1