Table 17 – ESEW & ESER Dual-Circuit Chiller Electrical Data (60 Hz)
Model
Main Power (3-phase, 60 Hz)
Compressors
Chiller
Rated
Allowable
Qty
RLA
1
LRA
2
MCA
3
MOPD
4
Min
Max
(each)
(each)
ESEW-020D &
ESER-020D
208
187
253
4
19.0
123
81
100
230
187
253
4
19.0
123
81
100
460
414
508
4
9.7
62
42
50
575
518
632
4
7.4
50
32
35
ESEW-030D &
ESER-030D
208
187
253
4
29.5
195
126
150
230
187
253
4
29.5
195
126
150
460
414
508
4
14.7
95
63
70
575
518
632
4
12.2
80
52
60
ESEW-040D &
ESER-040D
208
187
253
4
33.3
239
142
175
230
187
253
4
33.3
239
142
175
460
414
508
4
17.9
125
76
90
575
518
632
4
12.8
80
55
60
ESEW-050D &
ESER-050D
208
187
253
4
51.3
300
219
250
230
187
253
4
51.3
300
219
250
460
414
508
4
23.1
150
99
110
575
518
632
4
19.9
109
85
100
ESEW-060D &
ESER-060D
208
187
253
4
55.8
340
238
250
230
187
253
4
55.8
340
238
250
460
414
508
4
26.9
173
115
125
575
518
632
4
23.7
132
101
110
ESEW-080D &
ESER-080D
208
187
253
4
72.4
538
308
350
230
187
253
4
72.4
538
308
350
460
414
508
4
30.8
229
131
150
575
518
632
4
25.0
180
107
125
ESEW-0100D
& ESER-0100D
208
187
253
4
85.3
605
363
400
230
187
253
4
85.3
605
363
400
460
414
508
4
37.8
320
161
175
575
518
632
4
34.6
250
148
175
ESEW-0120D
& ESER-0120D
208
187
253
4
109.6
599
466
500
230
187
253
4
109.6
599
466
500
460
414
508
4
54.5
310
232
250
575
518
632
4
49.4
239
210
250
ESEW-0160D
& ESER-0160D
208
187
253
4
N/A
N/A
N/A
N/A
230
187
253
4
N/A
N/A
N/A
N/A
460
414
508
4
73.0
368
311
350
575
518
632
4
N/A
N/A
N/A
N/A
1
RLA is Rated Load Amps.