Installation - Remote Air-
Cooled Condenser
The remote condenser usually ships separately and
from a different location than the chiller.
Location
Chillers with a remote air-cooled condenser use a
separate remote air-cooled condenser. The
condenser is for outdoor use. A primary concern
when designing your unit was serviceability;
therefore, the condenser should be located in an
accessible area. Install the unit on a firm, level base
no closer than their width from walls or other
condensers. Avoid locations near exhaust fans,
plumbing vents, flues, or chimneys. Fasten the
mounting legs at their base to the steel or concrete
of the supporting structure. For units mounted on a
roof structure, the steel support base holding the
condenser should be elevated above the roof and
attached to the building.
Avoid areas that can create a “micro-climate” such as
an alcove with east, north, and west walls that can be
significantly warmer than surrounding areas. The
condenser needs to have unrestricted airways so it
can easily move cool air in and heated air away.
Consider locating the condenser where fan noise
and vibration transmission into nearby workspaces is
unlikely.
Allow a minimum of the width of the remote
condenser in clearance between the remote
condenser and any walls or obstructions. For
installations with multiple condensers, allow a
minimum of the width of the largest remote
condenser between condensers.