Home - System Overview
System Overview
The System Overview Screen (Home Screen) provides an overall synopsis of the chiller system. It also provides
quick links to other views as well as additional information.
Figure 19 – ESEW System Overview
Figure 20 – ESER System Overview
Table 23 – System Overview Functions
Function
Description
Screen Reference
Circuit Status
Messaging
Informs the operator of the chiller operation state as well as the status of the
circuits(s)
None
Alarm
Messaging
Provides information about any warnings or alarms which may have occurred.
Touching the Alarm Messaging banner will display the currently active alarms.
None
Setpoint
Modify the Setpoint by touching the current Setpoint on the HMI. An authorized
security level password is required to enter a new Setpoint.
None
Process Indicator
(PV)
The chiller can be set to control entering or leaving water temperatures. A “(PV)”
appears after the temperature used for temperature control. As standard the
systems is set for leaving water temperature control, which is suitable for systems
with a large system volume and a buffer tank. Return water temperature control is
mainly for systems with a smaller system fluid volume.
None
Menu Button
Changes to the Menu 1 screen
Full Screen
Display Mode
Will display only the Setpoint and process temperature in a large visible font
Alarms
A listing of active and prior alarm history
Detail
Additional circuit related information
Multiple
Pumps
Pump Control (Optional)
Warning
A listing of all active warnings
Start / Stop
Pressing START will start this chiller as well as any other networked chillers
attached to this system if they exist. The Start button will disappear at this point.
Pressing the STOP button will stop all chillers.
None