Table 22 – Dual-Circuit Remote Condenser Electrical Data (60 Hz)
Model
Main Power
(3-phase, 60 Hz)
Variable-Speed Fan
(1-phase)
Constant Speed Fans
(3-phase)
Total
FLA
2
MCA
3
MOP
4
Rated
Allowable
Qty
Motor
FLA
1
Qty
Motor
FLA
1
Min
Max
(hp)
Each
(hp)
Each
KCM034
208
187
253
2
½
3.6
2
¾
2.3
9.2
9.8
15
230
187
253
2
½
3.6
2
¾
2.3
9.2
9.8
15
460
414
508
2
½
1.7
2
¾
1.2
4.6
4.9
15
575
518
632
2
½
1.4
2
¾
0.9
3.6
3.8
15
KCL047
208
187
253
2
½
3.6
2
2
6.6
26.4
31.0
35
230
187
253
2
½
3.6
2
2
6.6
26.4
31.0
35
460
414
508
2
½
1.7
2
2
3.1
12.4
16.0
20
575
518
632
2
½
1.4
2
2
2.5
10.0
10.6
15
KCL060
208
187
253
2
½
3.6
2
2
6.6
26.4
31.0
35
230
187
253
2
½
3.6
2
2
6.6
26.4
31.0
35
460
414
508
2
½
1.7
2
2
3.1
12.4
16.0
20
575
518
632
2
½
1.4
2
2
2.5
10.0
10.6
15
KCL074
208
187
253
2
½
3.6
2
2
6.6
26.4
31.0
35
230
187
253
2
½
3.6
2
2
6.6
26.4
31.0
35
460
414
508
2
½
1.7
2
2
3.1
12.4
16.0
20
575
518
632
2
½
1.4
2
2
2.5
10.0
10.6
15
KCL090
208
187
253
2
½
3.6
4
2
6.6
39.6
46.0
50
230
187
253
2
½
3.6
4
2
6.6
39.6
46.0
50
460
414
508
2
½
1.7
4
2
3.1
18.6
21.0
25
575
518
632
2
½
1.4
4
2
2.5
15.0
16.0
20
KCL112
208
187
253
2
½
3.6
4
2
6.6
39.6
46.0
50
230
187
253
2
½
3.6
4
2
6.6
39.6
46.0
50
460
414
508
2
½
1.7
4
2
3.1
18.6
21.0
25
575
518
632
2
½
1.4
4
2
2.5
15.0
16.0
20
KCL137
208
187
253
2
½
3.6
6
2
6.6
52.8
61.0
70
230
187
253
2
½
3.6
6
2
6.6
52.8
61.0
70
460
414
508
2
½
1.7
6
2
3.1
24.8
31.0
35
575
518
632
2
½
1.4
6
2
2.5
20.0
21.0
25
KCL190
208
187
253
2
½
3.6
8
2
6.6
66.0
81.0
90
230
187
253
2
½
3.6
8
2
6.6
66.0
81.0
90
460
414
508
2
½
1.7
8
2
3.1
31.0
36.0
40
575
518
632
2
½
1.4
8
2
2.5
25.0
31.0
35
KCL224
208
187
253
2
½
3.6
10
2
6.6
79.2
91.0
100
230
187
253
2
½
3.6
10
2
6.6
79.2
91.0
100
460
414
508
2
½
1.7
10
2
3.1
37.2
46.0
50
575
518
632
2
½
1.4
10
2
2.5
30.0
36.0
40
1
FLA is Full Load Amps.
2
Total FLA as provided by the remote condenser manufacture.
3
MCA is Minimum Circuit Amps (for wire sizing) as provided by the remote condenser manufacturer.
4
MOP is Maximum Over-current Protection as provided by the remote condenser manufacturer.