4.4 Input Connections
WARNING
y
INPUTS MUST bE PROTECTED bY A LISTED CIRCUIT
bREAKER OR bRANCH RATED FUSE. THE CIRCUIT
bREAKER OR FUSE MUST bE RATED 375A MAX.
y
MULTIPLE POWER SOURCES ARE PRESENT, ENSURE
ALL INPUT POWER FEEDS ARE NOT ENERGIZED bEFORE
INSTALLING THEM. ELECTRICAL INSTALLATION SHOULD
ONLY bE PERFORMED bY QUALIFIED PERSONNEL WITH
PROPER TOOLS AND PROTECTIVE SAFETY EQUIPMENT.
NOTICE
y
MAKE SURE THAT ALL FEEDER CAbLES HAVE
HEAT SHRINK APPLIED PRIOR TO TERMINATION,
AND THAT NO-OXIDE COMPOUND IS APPLIED TO
ALL COPPER-TO-COPPER CONNECTIONS.
y
SEE APPENDIX C ON PAGE 19 FOR COMPRESSION LUG
SPECIFICATIONS, TOOLING, AND ORDERING INFORMATION.
TAbLE 3. INPUT TERMINATION SPECIFICATIONS
TERMINATION
TYPE
HOLE/STUD
SIZE
CENTER TO CENTER
RECOMMENDED TORQUE
VALUE
Threaded Stud
3/8 in.
1 in.
250 in∙lbs
Step 1.
Flip up the hinged plastic input cover.
Step 2.
Install the RTN cables/lugs to the RTN input studs located on the rear of the
panel
(see Figure 5)
. Ensure that all hardware is tightened.
Step 3.
Install the HOT input cables/lugs to the HOT input studs located on the rear of
the panel
(see Figure 6)
. Ensure that all hardware is tightened.
Step 4.
Reinstall the input safety cover from Step 1.
WARNING
FAILURE TO REINSTALL THE INPUT SAFETY COVERS
WILL CREATE AN ELECTRICAL HAZARD.
Figure 5. RTN Input Landing
Figure 6. HOT Input Landing
Содержание v30/30
Страница 1: ...SETUP AND OPERATION MANUAL F O R T E L E C O M B R O A D B A N D v30 30 Distribution Panel...
Страница 3: ...SETUP AND OPERATION MANUAL F O R T E L E C O M B R O A D B A N D v30 30 Distribution Panel...
Страница 6: ...V30 30 DISTRIBUTION PANEL SETUP AND OPERATION MANUAL PAGE vi THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...V30 30 DISTRIBUTION PANEL SETUP AND OPERATION MANUAL PAGE 8 Installation THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 29: ...THIS PAGE INTENTIONALLY LEFT BLANK...