ie-ms2-MS6-10
55
With inputs for resistance measurement and RTD transmitters current is connected to measured
resistance only during measurement.
Input for 2-wire measurement of resistance (0 to 300) ohm
Range:
(0 to 300) ohms
Accuracy:
0.1 % from range (±0.3 ohms)
Measuring current:
cca 0.8 mA at pulse approx. 50ms length
Input terminals:
IN and COM
Input for 2-wire measurement of resistance (0 to 3000) ohm
Range:
(0 to 3000) ohms
Accuracy:
0.1 % from range (±3 ohms)
Measuring current:
cca 0.5 mA at pulse approx. 50ms length
Input terminals:
IN and COM
Input for 2-wire measurement of resistance (0 to 10000) ohm
Range:
(0 to 10 000) ohms
Accuracy:
0.1 % from range (±10 ohms)
Measuring current:
cca 0.1 mA at pulse approx. 50ms length
Input terminals:
IN and COM
Input for 2-wire measurement of resistance transmitter Pt100
Measured value:
temperature from RTD sensor Pt100/ 3850 ppm
Range:
(-
200 .. 600) °C
Accuracy (without
probe):
±0.2 ° at range (
-
200..100) °C,
±0.2 % from value at range (100 .. 600) °C
Measuring current:
cca 0.8 mA at pulse approx. 50ms length
Input terminals:
IN and COM
Input for 2-wire measurement of resistance transmitter Pt1000
Measured value:
temperature from RTD sensor Pt1000/ 3850 ppm
Range:
(-
200 .. 600) °C
Accuracy (without
probe):
±0.2 °C at
range (-
200..100) °C,
±0.2 % from value at range (100 .. 600) °C
Measuring current:
cca 0.5 mA at pulse approx. 50ms length
Input terminals:
IN and COM
Input for 2-wire measurement of resistance transmitter Nickel 1000
Measured value:
temperature from RTD sensor Ni1000/ 6180 ppm
Range:
(-
50 .. 250) °C
Accuracy (without
probe):
±0.2 °C at range (
-
200..100) °C,
±0.2 % from value at range (100 .. 250) °C
Measuring current:
cca 0.5 mA at pulse approx. 50ms length
Input terminals:
IN and COM
Input for 2-wire measurement of NTC thermistor*
Measured value:
temperature from user definable NTC thermistor
For further information see Appendix No.11.
Range:
lowest measured temperature corresponds to maximum
measurable resistance of 11 000 ohms
Accuracy:
according to the used resistance range (300/3000/10 000 ohms)
Measuring current:
according to the used resistance range
Input terminals:
IN and COM
* This feature is available for MS6 firmware version 6.2.0 or later.