Connection of RTD transmitters and other resistance transmitters
data logger enables two-wire connection
use sufficient wire cross section and minimum cable lengths (errors caused by cable
resistance are specified in Appendix No. 6)
cable resistance measurement error can be compensated by suitable data logger setting
Connection of binary inputs
If input is configured as binary, potential-less contact or open collector or voltage levels can
be connected
read parameters of the input in chapter
Technical parameters of inputs
Connection of transmitters with RS485 digital output to RS485 input
Use suitable shielded twisted two-wire, e.g. 2x0.5 mm
2
, if using cable SYKFY 2x2x0.5 mm
2
,
spare pair can be used for transmitter powering.
It is recommended to terminate the link with resistor 120
at the beginning and the end of
the link. For shorter distances termination resistor can be omitted.
NOTE - only devices communicating at the same communication speed and
same protocol can be connected to the input !
input is galvanically isolated from data logger
available source +24V can be used for powering of transmitters (for its load rating
see section
Technical parameters of inputs