6.7.
Bookmark Ch..Alarms and indication
Two alarm states for each channel are enabled to define. Several actions are enabled to assign to each
alarm. Alarms are defined based on validity of Conditions or based on logical Combinations of conditions
(maximum four conditions from different channels).
Wiring diagram of possibility of alarm states creation and associated actions:
Example of alarm creation at used logical combination of conditions:
Alarm is active, if input conditions are valid. By means of combination of conditions you can solve also
complex situations including remote control. Some actions last during all alarm time (audible indication,
ALARM OUT output activity, visual indication, relay closing), other actions last only at the moment of
alarm creation (SMS message, e-mails). Changes of ALARM OUT output state or all alarms state can be
recorded.
condition num. 3 on
channel 2
condition num.2 on
channel 5
condition num. 4 on
channel 1
condition num. 1 on
channel 2
alarm is activated, if equation is valid:
(condition 3 on channel 2 AND condition 2 on channel 5)
OR
(condition 4 on channel 1 AND condition 1 on channel 2)
ALARM2
on channel 10
activated
measured
value
condition num. 1
(2,3,4)
is valid
ALARM 1
activated
yellow LED shines (always)
internal audio indication
activate ALARM OUT sig.
SMS & e-mail sending, SNMP...
selected relay activation
condition num. 2
(1,3,4)
is valid
ALARM 2
activated
red LED shines (always)
internal audio indication
activate ALARM OUT sig.
SMS & e-mail sending, SNMP...
selected relay activation