For MS6: use original included screws to mount side brackets or DIN rail holder. Using
longer crews can cause reduction of insulation distance between screws and printed circuit
board or short circuits. This can cause system functionality and safety of the users!
For MS6-Rack: Do not connect
to
MP050 terminals higher voltage than 50V AC/75V DC
Connect MP018 module (for MS6, MS6D, MS6R) to data logger with special cable MP017 (see its
wiring in Appendix No. 4 including drawing of connection terminals to this module). Connect module when
data logger is switched off! Plug one cable end to corresponding connector on relay module, second end to
data logger, connector Ext. Terminal & Relays (upper or lower connector half can be used, both parts are
connected identically). Connect slave device on output terminals of relay. Pay attention to necessary safety
(depending on the character of connected device). Connect MP050 module (for MS6-Rack only) with
included cable to internal terminal of data logger behind Ext. terminal output. Relay module must be
activated for proper function by means of SW
–
see Appendix No. 5. If data logger is delivered together
with this module, function is activated from the manufacturer.
3.4.
Mounting and connection of external terminal with display
External terminal with display is designed for visualization of measured values, alarms and for data
logger controlling from point up to maximum 50 m from data logger. Its function is identical with internal
built-in display of MS6 (keyboard and display work in parallel). The part of the display is also audio
indication working analogically as external audio indication unit connected to output ALARM OUT.
External terminal is delivered in two versions. As a module prepared for installing to suitable case or
in compact case. Module version can be mounted to the lid of light current switchboard or to stand alone
case. Cut rectangle opening 156 x 96 mm to the lid, install terminal module. Insert four screws from front
side and screw them to metal holders from the inside. Tighten screws slightly from front side and cover
with blinders.
Connect external terminal to data logger with special cable (wiring diagram is specified
in Appendix No. 4). Connect when data logger is switched off! Follow identical rules for cable
routing as for input signals. Plug one cable end to corresponding connector on display unit, second
end to data logger, connector Ext. Terminal & Relays (upper or lower connector half can be used,
both parts are connected identically).
External terminal must be activated for proper function by means
of SW
–
see Appendix No. 5. If data logger is delivered together with this module, function is activated
from the manufacturer.
3.5.
Connection of data logger to the computer
Data logger contains for communication with computer one internal communication interface, which is
separated to several external interfaces. Data logger communicates only via one selected interface:
Содержание MS6D
Страница 1: ...MONITORING DATA LOGGING AND CONTROL SYSTEM MS6D MS6R INSTRUCTION MANUAL Basic Part...
Страница 4: ...4 ie ms2 MS6 10 Drawing of MS6 Rack Drawing of MS6 Rack with output relays module MP050...
Страница 5: ...ie ms2 MS6 10 5 Architecture of measuring system with data logger MS6D MS6R...