Reflect-O-Ray
®
Oil Fired EDS 3.5
Installation, Operation & Service
Page 34
Combustion Research Corporation
BURNER SETUP DATA
Each
Reflect-O-Ray
®
Oil Fired EDS 3.5
®
burner assembly
is marked with the input firing rate and fuel designation on
the name plate. Refer to the following chart for correct
manifold pressure and vacuum readings.
When the system is equipped with fresh air inlet ducting,
the vacuum reading must be read as a differential across
the entire burner. Use the 1/8" NPT (
3.2mm
) test plugs
located on the 4" dia. inlet and air box of the burner. See
diagram below. Each
Reflect-O-Ray
®
Oil Fired EDS 3.5
burner assembly is marked with the input firing rate and
fuel designation on the nameplate. Refer to the following
chart for correct manifold pressure and vacuum readings.
Use only #2 Fuel Oil (@ 140,000 Btu/Gal.). Do not attempt
to burn waste oil, garbage, or paper with this system.
When the system is equipped with fresh air inlet ducting,
the vacuum reading must be read as a differential. Use the
1/8" NPT (
3.2mm
) test plugs located on the 4" dia. inlet
and air box of the burner. See diagram below.
The following chart shows two types of Riello burner
heads. The MECTRON 3 (M3) head was used prior to
the 93/94 heating season and the Riello 40 F3 series is
used thereafter.
BURNER PART NO.
BTU/Hr INPUT
MAX. GPH
VACUUM READING HOT*
0500.R
125,000
0.89 GPH
0.4” – 0.5” W.C.
0510.R
105,000
0.75 GPH
0.4” – 0.5” W.C.
0520.R
70,000
0.50 GPH
0.4” – 0.5” W.C.
* NOTE
– The systems must be operating for a minimum of 15 minutes prior to taking any
readings. The vacuum settings are for systems equipped for use with either inside (indoor) or
outside (outdoor) combustion air.
NOZZLE SIZE
BURNER OIL PRESSURE
BURNER
PART NO.
BTU/Hr
INPUT
ELECTRICAL RATING
40 F3
MECTRON 3
40 F3
MECTRON 3
0500.R
125,000
120V, 1.6 Amp. (4.0 FLA)
.70-60°
HOLLOW
.70-60° SOILD
150 PSI
140 PSI
0510.R
105,000
120V, 1.6 Amp. (4.0 FLA)
.65-60°
HOLLOW
.65-60° SOLID
150 PSI
140 PSI
0520.R
70,000
120V, 1.6 Amp. (4.0 FLA)
.50-60°
HOLLOW
.50-60° SOILD
150 PSI
140 PSI
BURNER
PART NO.
COMBUSTION AIR
ORIFICE SIZE
40 F3
MECTRON 3
40 F3
MECTRON 3
ALTITUDE
0500.R
2.0”
4
7
3
3
0 - 4500FT (0 -1370 m)
0510.R
1.75”
3.6
5
2
2
0 - 4500FT (0 -1370 m)
0520.R
1.5”
2.6
3.2
0.5
0
0 - 4500FT (0 -1370 m)
1/8” NPT TEST PLUG
(Location may be on
chamber side)
1/8” NPT TEST PLUG
(Use this test port when
a differential vacuum
reading is required)
REAR VIEW
(Air Inlet side of Burner
Assembly)