Reflect-O-Ray
®
Oil Fired EDS 3.5
Installation, Operation & Service
Page 16
Combustion Research Corporation
DECORATIVE GRILLE INSTALLATION
CAUTION
CUT HAZARD - SHARP EDGES.
Wear protective gloves when installing and handling
aluminum decorative grille and side shields. Failure to
follow these instructions will result in personal injury.
When installing the heating system above a suspended
ceiling, unpainted aluminum decorative grille must be used
directly beneath the radiant tube system. The use of regular
ceiling tiles directly beneath the radiant tube will create an
unsafe condition.
The unpainted aluminum decorative grille provides an
attractive finish to the system when installed over a
suspended ceiling. The aluminum Decorative Grille (PN
0369.00) comes in standard 2 ft. x 4 ft. (60 cm x 120 cm)
sections and is installed in place of the ceiling tile. The
decorative grill should extend completely under all of the
radiant tube as well as the burner assembly.
The radiant tube is suspended in normal fashion, centered
over the decorative grille. The radiant tube must be
installed, as shown below, with a minimum distance from the
radiant tube to the decorative grille of 6" (15.2 cm) to a
maximum of 10" (25.4 cm).
"T" bar heat shields (PN 0369.21) must be installed over
ceiling "T" frame members that pass underneath the radiant
tube. The Decorative Grille Side Shield reflector (PN
0369.11) is available in 10-ft. (3 m) lengths. Lay the side
shield along the standard reflector and cut suitable notches
for the reflector hangers and "T" bar sections. As sharp
edges can be encountered when working the aluminum
decorative grille and side shields, gloves should be worn.
"T" Bar Heat Shield
P.N. 0369.21
Suspended Ceiling
"T" Bar Framing
Decorative Grille
2 ft. (60 cm) Wide
Decorative Grille
Side Shield (10’ Long)
P.N. 0369.11
Reflector and
Radiant tube
Cut Relief Notches in Side Shield to
Accommodate Tube & Reflector Hangers
!
Содержание reflect-o-ray eds 3.5
Страница 4: ......
Страница 57: ...Reflect O Ray Oil Fired EDS 3 5 Installation Operation Service Combustion Research Corporation Page 53 NOTES...
Страница 60: ......
Страница 61: ......